Technical Data TD00405018E
Effective August 2009
Generator Sizing Guide
EATON CORPORATION www.eaton.com
Table 2. Non - Motor Load Reference
Residential
Description
Running Load*
Running kW
Amps @
120V 1Ø
Amps @
240V 1Ø
Electric heat per 1000 ft2 12 N/A 50
Heat pump elements per 1000 ft2 7 N/A 29
Dryer 5.5 N/A 23
Hot tub 10 N/A 50
Range oven/Stove top per burner 8 N/A 30
Hot water 4.5 N/A 19
General lighting and receptacles
per 1000 ft2
3 24.9 N/A
Blow dryer 1.25 10.4 N/A
Dishwasher 1.5 12.5 N/A
Microwave 1 8.3 N/A
Toasters 1 8.3 N/A
Home Entertainment Center 1 8.3 N/A
Computer 1 8.3 N/A
Kitchen 1.5 12.5 N/A
Laundry 1.5 12.5 N/A
Commercial
Please refer to equipment data plate and/or billing history for commercial details
* Always check data plate for actual running amps.