UPS OPERATING INSTRUCTIONS
EATON Powerware
®
9395 UPS (450–550 kVA) Installation and Operation Manual S 164201701 Rev 2 www.powerware.com
7−16
5. Press the SELECT pushbutton on the UPS Command menu bar.
The UPS transfers to Energy Saver mode and the critical load is immediately
supplied by the bypass source. If the bypass source is not available, the power
module remains on and an alarm sounds.
The
NORMAL status indicator is illuminated. The UPS status indicates ENERGY
SAVER. The Bypass status indicates ON. The UPM status indicates ONLINE. If
the battery is not charging, the power module is off.
7.3.8 Transfer from Energy Saver to Normal Mode
To transfer the critical load to Normal mode:
NOTE The Energy Saver mode commands are displayed only if enabled at the factory or by an Eaton
Customer Service Engineer.
1. Press the CONTROLS pushbutton on the main menu bar. The System Status
screen is displayed.
2. On the System Status screen, select the
UPS command.
3. Press the CONTROLS pushbutton on the System Status menu bar. The UPS
Control Command screen is displayed.
4. On the UPS Control Command screen, select
GO TO NORMAL.
5. Press the
SELECT pushbutton on the UPS Command menu bar.
The UPS transfers to Battery mode and then to Normal mode. If the power
module is not available, the system remains on bypass and an alarm sounds.
The
NORMAL status indicator is illuminated. The UPS status indicates ONLINE.
The UPM status indicates ONLINE.
7.3.9 Transfer from Normal to High Alert Mode
To transfer the critical load to High Alert mode:
NOTE The High Alert mode commands are displayed only if enabled at the factory or by an Eaton Customer
Service Engineer.
1. Press the CONTROLS pushbutton on the main menu bar. The System Status
screen is displayed.
2. On the System Status screen, select the UPS command.
3. Press the
CONTROLS pushbutton on the System Status menu bar. The UPS
Control Command screen is displayed.
4. On the UPS Control Command screen, select GO TO HIGH ALERT.