Available settings
If Bypass transfer is enabled,
Interrupt time: [10ms] [20ms]
Define break duration when transfer
on Bypass
[10%] … [102%]
Load % when overload alarm occurs
[Unitary UPS] [Hot Standby]
Force slew rate value to 0.5Hz/s
[Enabled] [Disabled]
Authorize the product to start on
battery power.
[Enabled] [Disabled]
If mains recover during a shutdown
sequence:
If set to Enabled, shutdown sequence
will complete and wait 10 seconds
prior to restart,
If set to Disabled, shutdown
sequence will not complete and
restart will occur immediately.
[Enabled] [Disabled]
Authorize the product to restart
automatically when mains recovers
after a complete battery discharge.
[Enabled] [Disabled]
The UPS automatically starts up as
soon as mains power is available
(no need topress the
button).
[Disabled] [100W] … [1000W]
If Enabled, UPS will shutdown after
5 min
.
of back-up time, if load is less
than threshold.
[Enabled] [Disabled]
If Disabled, LCD and communication
will turn OFF immediately after UPS
is OFF
.
If Enabled, LCD and communication
stays ON 1h30 min after UPS is OFF.
[Enabled] [Disabled]
If Enabled, shutdown or restart
commands from software are
authorized.
[Enabled] [Disabled]
Define if output is powered from
Bypass in Standby mode.
In constant charge mode:
[No test] [Every day] [Every week]
[Every month]
In ABM cycling mode :
[No test] [Every ABM cycle]
[0%]
... [100%]
The alarm triggers when the set
percentage of battery capacity is
reached during back-up time.
[0%]
... [100%]
If set, automatic restart will occur
only when percentage of battery
charge is reached.
[ABM cycling] [Constant charge]
[Auto detection]
[Auto detection]
[Manual EBM set.]
Using standard EBM, UPS
[Manual battery set.]
detects automatically the
[No battery]
number of EBM connected
[Yes] [No]
[Yes]
If set to Yes, the UPS automatically
prevents battery from deep discharge
by adapting end of back-up time
voltage threshold
.
Warranty void if set to No.
5-6kVA EU_EN
Submenu
Interrupt time
Overload
prealarm
Redundancy
mode
Cold start
Forced reboot
uto restart
uto start
Energy saving
Sleep mode
Remote command
Bypass standby
Automatic battery
test
Low battery
warning
Restart bat
.
level
Battery settings
Battery charge
mode
External battery
Deep Disch.
protect.
Page 14
Default settings
[10ms]
[102%]
Unitary UPS
[Enabled]
[Enabled]
[Enabled]
[Disabled]
[Disabled]
[Enabled]
[Enabled]
[Enabled]
[Every ABM cycle]
[20%]
[0%]
[ABM cycling]
2
. Presentation
In/Out settings
On/Off settings