Available settings
If Bypass transfer is enabled,
Interrupt time: [10ms] [20ms]
Define break duration when transfer
on Bypass
[10%] … [102%]
Load % when overload alarm occurs
[Unitary UPS] [Hot Standby]
Force slew rate value to 0.5Hz/s
[Enabled] [Disabled]
Authorize the product to start on
battery power.
[Enabled] [Disabled]
If mains recover during a shutdown
sequence:
If set to Enabled, shutdown sequence
will complete and wait 10 seconds
prior to restart,
If set to Disabled, shutdown
sequence will not complete and
restart will occur immediately.
[Enabled] [Disabled]
Authorize the product to restart
automatically when mains recovers
after a complete battery discharge.
[Enabled] [Disabled]
The UPS automatically starts up as
soon as mains power is available
(no need topress the
button).
[Disabled] [100W] … [1000W]
If Enabled, UPS will shutdown after
5 min
.
of back-up time, if load is less
than threshold.
[Enabled] [Disabled]
If Disabled, LCD and communication
will turn OFF immediately after UPS
is OFF
.
If Enabled, LCD and communication
stays ON 1h30 min after UPS is OFF.
[Enabled] [Disabled]
If Enabled, shutdown or restart
commands from software are
authorized.
[Enabled] [Disabled]
Define if output is powered from
Bypass in Standby mode.
In constant charge mode:
[No test] [Every day] [Every week]
[Every month]
In ABM cycling mode :
[No test] [Every ABM cycle]
[0%]
... [100%]
The alarm triggers when the set
percentage of battery capacity is
reached during back-up time.
[0%]
... [100%]
If set, automatic restart will occur
only when percentage of battery
charge is reached.
[ABM cycling] [Constant charge]
[Auto detection]
[Auto detection]
[Manual EBM set.]
Using standard EBM, UPS
[Manual battery set.]
detects automatically the
[No battery]
number of EBM connected
[Yes] [No]
[Yes]
If set to Yes, the UPS automatically
prevents battery from deep discharge
by adapting end of back-up time
voltage threshold
.
Warranty void if set to No.
5-6kVA EU_EN
Submenu
Interrupt time
Overload
prealarm
Redundancy
mode
Cold start
Forced reboot
A
uto restart
A
uto start
Energy saving
Sleep mode
Remote command
Bypass standby
Automatic battery
test
Low battery
warning
Restart bat
.
level
Battery settings
Battery charge
mode
External battery
Deep Disch.
protect.
Page 14
Default settings
[10ms]
[102%]
Unitary UPS
[Enabled]
[Enabled]
[Enabled]
[Disabled]
[Disabled]
[Enabled]
[Enabled]
[Enabled]
[Every ABM cycle]
[20%]
[0%]
[ABM cycling]
2
. Presentation
In/Out settings
On/Off settings