Introduction
Eaton BladeUPS 5.1 kVA to 60 kVA (N+1) User’s Guide 164201649—Rev 9 www.eaton.com/powerquality 4
Note the following guidelines when configuring your BladeUPS standalone module or parallel system:
l
The UPS accommodates a maximum of four EBMs.
l
The EBM(s) for a standalone UPS can be mounted directly below the UPS or, with rack side panels removed,
in an adjacent rack to the left or right of the rack containing the UPS.
l
The EBMs for a parallel system can be mounted in an adjacent rack to the left or right of the rack containing
the UPS (rack side panels removed).
l
When configured with EBMs, each UPS in a parallel system must have the same number of EBMs installed.
l
BladeUPS requires input phase rotation of A-B-C clockwise. Some load equipment may require phase
rotation or phase relationship coordination to ensure proper operation. Review your equipment
manufacturer’s power requirement documents to ensure that your connected equipment operates correctly.