UPS Maintenance
Eaton BladeUPS 5.1 kVA to 60 kVA (N+1) User’s Guide 164201649—Rev 9 www.eaton.com/powerquality 126
Figure 85. Removing the UPS Front Cover and Electronics Module
4. Label the original module with masking tape or some other identifier. Record the serial number of the
replacement module for your warranty.
If not returning the electronics module for warranty, see the following section, “Recycling the Used
Battery or UPS” on page 129 for proper disposal.
5. Insert the replacement module by sliding it carefully into the cabinet. Verify that it seats firmly against the
rear of the cabinet.
Reinstall the electronics module locking screw.
6. Parallel configurations only. Reconnect the redundant signal cable(s).
7. Replace the UPS front cover (see Figure 86):
Plug the LCD cable from the control panel on the front cover into the connector on the electronics
module. Use care to loop the LCD cable gently in front of the electronics module.
Push the top of the front cover firmly into place, and then push the bottom firmly into place.
8. Verify that no alarms are indicated on the control panel.
9. Transfer the UPS to Normal mode.
Electronics Module
Locking Screw
Ring Handle
LCD Cable