Specifications
Eaton BladeUPS 5.1 kVA to 60 kVA (N+1) User’s Guide 164201649—Rev 9 www.eaton.com/powerquality 137
Input Power Factor
High Efficiency setting: load dependent
Standard setting: >0.99
Input Mode Three-phase
Input Source
5-wire with continuous neutral.
NOTE: Contact your Eaton UPS sales specialist for operation with 4-pole ATS switches.
Table 23. Electrical Input
BladeUPS 12 Model BladeUPS 12i Model BladeUPS 8 Model BladeUPS 5.1 Model
Table 24. Electrical Output
BladeUPS 12 Model BladeUPS 12i Model BladeUPS 8 Model BladeUPS 5.1 Model
Nominal Output Voltage 120/208 Vac three-phase 230/400 Vac three-phase 120/208V three-phase 120/208V three-phase
Output Voltage Variation
104–132 Vac phase to neutral,
180–229
Vac phase to phase
207–253 Vac phase to
neutral,
358–438
Vac phase to
phase
104–132 Vac phase to
neutral,
180–229 Vac phase to
phase
104–132 Vac phase to
neutral,
180–229 Vac phase to
phase
Connections
IEC 309-60A power cord IEC 309-32A power cord NEMA L21-30P NEMA L21-20P
For paralleling, a single Anderson input/output cord connects to the
BladeUPS Bar (see Table 19 on page 135).
Short Circuit Capability
(Battery
Mode)
84A, <300 ms 44A, <300 ms 84A, <300 ms 84A, <300 ms
Short Circuit Capability
(Normal
Mode)
Limited by 50A input breaker Limited by 25A input
breaker
Limited by 50A input
breaker
Limited by 50A input
breaker
Nominal Output Frequency
50–60 Hz auto-detection (Normal mode)
50 or 60
Hz (Battery mode)
Output Frequency Variation
Synchronized (Normal mode)
±0.1 when not synchronized with source (Battery mode)
Output Overload
100–110%: load transfers to Bypass mode after 10 minutes
110–125%: load transfers to Bypass mode after 1 minute
125–150%: load transfers to Bypass mode after 5 seconds
>150%: load transfers to Bypass mode after 300
ms
Voltage Waveform
Standard mode and Battery mode: Sine wave; <2% THD with linear load;
<5% with nonlinear load
Full Output Three-phase
Table 25. Environmental and Safety
BladeUPS 12 Model BladeUPS 12i Model BladeUPS 8 Model BladeUPS 5.1 Model
Surge Suppression ANSI C62.41 Category B3 EN 61000-4-6 ANSI C62.41 Category B3 ANSI C62.41 Category B3
Safety Conformance
UL 1778 4
th
edition; CSA
C22.2, No. 107.3
UL 1778 4
th
edition, EN and
IEC
62040-1-1
UL 1778 4th edition; CSA
C22.2, No. 107.3
UL 1778 4th edition; CSA
C22.2, No. 107.3
Agency Markings cULus, ICES, CE cULus, CE cULus cULus
EMC (Class A) FCC Part 15 EN 62040-2 FCC Part 15 FCC Part 15
Operating Temperature
0°C to 40°C (32°F to 104°F)
Optimal battery performance: 5°C to 25°C (41°F to 77°F)
Storage Temperature 0°C to 25°C (32°F to 77°F)
Transit Temperature -25°C to 55°C (-13°F to 131°F)