Standard System Installation
Eaton BladeUPS 5.1 kVA to 60 kVA (N+1) User’s Guide 164201649—Rev 9 www.eaton.com/powerquality 79
Figure 64. Typical CAN Bridge Card and Redundant Signal Wiring
13. Install a redundant signal cable between the For Parallel Use Only and Standalone/Parallel terminals on
each UPS as shown in
Figure 64.
Be sure to check correct polarity when installing the cable.
CAUTION
If polarity or wiring is not correct, the parallel system does not operate normally. For example,
when shutting down one UPS, the remaining UPS transfers the load to bypass instead of
supporting the load. Verify that all wiring is correct for proper operation.
UPS 3
UPS 2
UPS 1
CAN Bridge Card Cable
CAN
IN
Blue Terminating Plug
Redundant Signal Cable
For Parallel
Use Only
Standalone/
Parallel
For Parallel
Use Only
Standalone/
Parallel
Standalone/
Parallel
(remove)
CAN
OUT
Blue Terminating Plug